• InFo Display
• CFG
Enabling self-
tuning,
autotuning,
softstart
CFG
Control parameters
Proportional band for
heating or hysteresis on
ON-OFF action
Integral time
for heating
Derivative time
for heating
Maximum power limit
for heating
Setpoint for cooling
relative to heating
setpoint
Proportional band for
cooling or hysteresis for
ON/OFF control
Integral time for cooling
Derivative time
for cooling
Maximum power limit
for cooling
Manual reset
Alarm 2 hysteresis
Alarm 3 hysteresis
Waiting time for HB alarm
intervention
Waiting time for LBA alarm intervention
(Set to “0” to disable LBA alarm)
Power limit for LBA
alarm condition
Power output in fault condition
(when probe is faulty)
(*)
(*)
15
16
17
18
19
20
21
22
23
24
25
31
33
34
35
36
S.tun Continuous Self-tuning Softstart
autotuning
0NONONO
1 YES NO NO
2 NO YES NO
3 YES YES NO
4NONOYES
5 YES NO YES
6---
7---
8 WAIT NO NO
9GO NO NO
10 WAIT YES NO
11 GO YES NO
12 WAIT NO YES
13 GO NO YES
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
-999 … 999
scale points
0.0 … 999.9%
full scale
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
± 25.0% f.s.
0.0 … 999.9%
full scale
± 999
scale points
± 999
scale points
0 ... 999
seconds
0.0 ... 500.0 min
-100.0 ... 100.0%
ON / OFF
-100.0 ... 100.0%
ON / OFF
Set gradient
(see applicable note)
0.0...999.9 digit/min.
(digit / sec see SP.ty)
Antireset
Feedforward
27
28
0 ... 9999
scale points
-100.0 ... 100.0%
Reset power
26
-100.0 ... 100.0%
(*) LBA alarm may be reset by simultaneously pressing ∆ + ∇ keys when OutP is displayed or by
switching to Manual.
216
INFO
Serial
communication
code
Software
version
Software
protection code
Self
diagnostic
error
code
8
9
10
11
12
Information
display
0 No Error
1Lo
2Hi
3 ERR
4 SBR
Alarm 1 hysteresis
30
± 999
scale points
Softstart time
29
0.0 ... 500.0 min
(Value has to be higher than cycle time value of
output to which HB alarm is assigned)
Minimum power limit for
heating (not available for
double heat/cool action)
254
0.0 ... 100.0%
Cooling medium
97
0 ... 2
Minimum power limit for
cooling (not available for
heating/cooling double
action)
255
0.0 ... 100.0%
C.MEd Relative gain (Rg)
(see applicable note)
0 Air 1
1 Oil 0,8
2 Water 0,4
Note:
h_Pb, h_it, h_dt, h.P.Hi, hPLo, c_Pb, c_it, c_dt, c.P.Hi, c.P.Lo parameters are “read only” if the option
“control parameter groups” has been selected (showing current values)
c_Pb, c_it, c_dt parameters are “read only” if the option “relative gain heat/cool control” (Ctrl = 14) has
been selected.
-
-
-
-
-
-
-
-
-
-
4