Page 8
80018C_MSW_2400-2500-Profibus_1209_ENG
59 Process Data Output 9 (MSB) (556) Alarm Point 5 LSW 02 (556) Alarm Point 2 LSW 02
60 Process Data Output 9 (LSB) 32 2C
61 Process Data Output 10 (MSB) (557) Alarm Point 5 MSW 02 (557) Alarm Point 2 MSW 02
62 Process Data Output 10 (LSB) 33 2D
63 Process Data Output 11 (MSB) (558) Alarm Point 6 LSW 02 (558) Alarm Point 3 LSW 02
64 Process Data Output 11 (LSB) 34 2E
65 Process Data Output 12 (MSB) (559) Alarm Point 6 MSW 02 (559) Alarm Point 3 MSW 02
66 Process Data Output 12 (LSB) 35 2F
67 Process Data Output 13 (MSB) (560) Alarm Point 7 LSW 02 (560) Alarm Point 4 LSW 02
68 Process Data Output 13 (LSB) 36 30
69 Process Data Output 14 (MSB) (561) Alarm Point 7 MSW 02 (561) Alarm Point 4 MSW 02
70 Process Data Output 14 (LSB) 37 31
71 Process Data Output 15 (MSB) (562) Alarm Point 8 LSW 02 (562) Alarm Point 5 LSW 02
72 Process Data Output 15 (LSB) 38 32
73 Process Data Output 16 (MSB) (563) Alarm Point 8 MSW 02 (563) Alarm Point 5 MSW 02
74 Process Data Output 16 (LSB) 39 33
The “Process Data” are freely configurable and correspond to the MODBUS address of the corresponding variable,
shown in the MODBUS MEMORY MAP document of the 2400/2500 instruments.
4.4 DIAGNOSTICS DATA REQUEST TELEGRAM (SAP 60)
When the PROFIBUS Master requests diagnostics data from the instrument, the instrument replies with 6 standard
data bytes and 3 bytes representing specific product diagnostics.
1 ≈ 6
In accordance with standard EN50170 -
7 Length of external diagnosis 2
8 MSB external diagnostics xx
9 LSB external diagnostics xx
With “xx=00” in absence of alarms and “xx=FF” with 2400/2500 in fault state.