EasyManuals Logo
Home>gefran>Controller>GFXTERMO4

gefran GFXTERMO4 User Manual

gefran GFXTERMO4
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
20
880397M_MSW_GFX4-GFXTERMO4_08-2018_ENG
ADVANCED SETTINGS
Input lter
FUNCTIONAL DIAGRAM
604
FLt.2
R/W
Digital filter for auxiliary input
0.0 ... 20.0 sec
0.1
Sets a low pass lter on the auxiliary input, running the average of values read in the
specied time interval. If = 0 , excludes the average lter on sampled values.
Auxiliary
input
Select sensor
(AI.2)
Scale limits, decimal
point, Offset (H.S2,
L.S2, dP.2 or FS.2)
Low pass f
ilter
(Flt.2)
Internal
variable In.2
See generic
alarms and
Control
602
In.2
R
Value of auxiliary input
606
Er.2
R
Error code for self-diagnosis
of auxiliary input
0 No error
1 Lo (value of process variable is < Lo.S)
2 Hi (value of process variable is > Hi.S)
3 ERR [third wire interrupted for PT100 or input values below minimum
limits (ex.: for TC with connection error)]
4 SBR (probe interrupted or input values beyond maximum limits)
Error code table
Read state