5180397M_MSW_GFX4-GFXTERMO4_08-2018_ENG
SOFTSTART
If enabled, this function partializes power based on a percentage of time elapsed since instrument switch-on compared
to the set time of 0.0 ... 500.0 min (“SoF” parameter CFG phase). Softstart is an alternative to selftuning and is activated after
each instrument switch-on. Softstart is reset when switching to manual.
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
0
S.tu Autotuning Selftuning Softstart
continuous
0 NO NO NO
1 YES NO NO
2 NO YES NO
3 YES YES NO
4 NO NO YES
5 YES NO YES
6 - - -
7 - - -
8* WAIT NO NO
9 GO NO NO
10* WAIT YES NO
11 GO YES NO
12* WAIT NO YES
13 GO NO YES
Selftuning, autotuning, softstart table
(*) +16 with automatic switching in GO if PV-SP > 0.5% f.s.
+32 with automatic switching in GO if PV-SP > 1% f.s.
+64 with automatic switching in GO if PV-SP > 2% f.s.
+128 with automatic switching in GO if PV-SP > 4% f.s.
Read state
147
SOF
R/W
Softstart time
0.0 ...500,0 min
0,0
63
bit
STATE SOFTSTART
OFF = Softstart in Stop
ON = Softstart in Start
R
263
SP.S
R/W
Softstart setpoint
(preheating hot runners)
0
264
SO.P
R/W
Softstart power
(preheating hot runners)
-100,00....
....100,0 %
0,0
START MODE
699
P.ONT
R/W
Start modes at Power-On
0
0* Function at previous state
1 Software shutdown
2 Software startup
(*) digital input states always have priority
68
bit
STATE OF DIGITAL
INPUT 1
OFF = Digital input 1 off
ON = Digital input 1 on
R
92
bit
STATE OF DIGITAL
INPUT 2
OFF = Digital input 2 off
ON = Digital input 2 on
R
See: Table of digital input functions
Read state
0
bit
SELFTUNING STATE
OFF = Selftuning in Stop
ON = Selftuning in Start
R
296
R
Autotuning and selftuning enable state
(FLG_PID)
Autotuning and selftuning enable status table
bit
3 Selftuning on