4180397M_MSW_GFX4-GFXTERMO4_08-2018_ENG
Set gradient
The “Set gradient” function sets a gradual variation
of the setpoint, with programmed speed, between two defined
values. If this function is active (
g.sp other than 0), at switch-
on and at auto/man switching the initial setpoint is assumed
equal to the PV, and the local or selected set is reached with
set gradient. Every variation of set, including variations of the
local setpoint, is subject to the gradient.
The value of remote setpoint SP.rS is not saved in eeprom.
The set gradient is inhibited at switch-on when self-
tuning is enabled.
265
xot
R/W
Select hot runner functions
0
Table of hot runner functions
Fault action
Enable power if PV is Enable
hot runners not stabilized preheating softstart
0 FA.P
1 X Average power
2 FA.P
3 X FA.P
4 FA.P X
5 X Average power X
6 FA.P X
7 X FA.P X
+8 enable GS.2
FA.P – see alarm for probe in short or connection error (SBR-ERR)
234
22
g.sp
R/W
Set gradient
0.0 ...999.9 digit / min
( digit / sec see SP.r )
0,0
259
g.s2
R/W
Set gradient relative to SP2
0.0 ...999.9 digit / min
( digit / sec see SP.r )
0,0
Multiset
The MULTISET function determines the local setpoint
by selecting the value from Setpoint 1 (SP.1) or from Setpoint
2 (SP.2) based on the state of a digital input or by setting from
a serial line.
The variation between Setpoint 1 and Setpoint 2
can take place with gradient: parameter G.SP determines the
speed for reaching Setpoint 1 and parameter G.S2 defines
the speed for reaching Setpoint 2.
The MULTISET function is enabled with parameter
hd.1 and automatically enables the gradient function.
Selection between Setpoint 1 and Setpoint 2 can be seen by
means of LED.
191
hd.1
R/W
Enable multiset:
control instruments via serial
0
Multiset table
Enable Enable
Multiset virtual instrument
0
1 X
2 X
3 X X
SETPOINT CONTROL
AL
Referred to current
setpoint
Setpoint profile
Setpoint < AL
Delay
(parameter HY.n)
Absolute alarm
Reverse alarm
Direct alarm
Time
(min. or sec.)
SP1
SP2
SPrem
SP1
(*)
ON
ON
SP
IN1
LOC/REM
t
t
t
(*) if set gradient is set
230
482
SP.1
R/W
Setpoint 1
100
231
483
SP.2
R/W
Setpoint 2
200
+16 For Heat/Cool control Ctr only: CT connected to cool output