62
880397M_MSW_GFX4-GFXTERMO4_08-2018_ENG
469
R
Instrument state 1
bit
0 AL.1 or AL.2 or AL.3 or AL.4 or ALHB.TA1 or ALHB.TA2 or ALHB.TA3 or Power Fault
1 Input Lo
2 Input Hi
3 Input Err
4 Input Sbr
7 LBA
8 AL.1
9 AL.2
10 AL.3
11 AL.4
12 AL.HB1
13 AL.HB2 (only for 3-phase load)
14 AL.HB3 (only for 3-phase load)
15 Selftuning on
Table of instrument state 1
632
R
Instrument state 2
bit
0 AL.1
1 AL.2
2 AL.3
3 AL.4
4 AL.HB1
5 AL.HB2(only for 3-phase load)
6 AL.HB3 (only for 3-phase load)
7 Input Lo
8 Input Hi
9 Input Err
10 Input Sbr
11 LBA
12 AL.Power
Table of instrument state 2
633
R
Instrument state 3
bit
0 SSR_OPEN1
1 SSR_OPEN2 (only for 3-phase load)
2 SSR_OPEN3 (only for 3-phase load)
3 SSR_SHORT1
4 SSR_SHORT2 (only for 3-phase load)
5 SSR_SHORT3 (only for 3-phase load)
6 NO_VOLTAGE1
7 NO_VOLTAGE2 (only for 3-phase load)
8 NO_VOLTAGE3 (only for 3-phase load)
9 NO_CURRENT1
10 NO_CURRENT2 (only for 3-phase load)
11 NO_CURRENT3 (only for 3-phase load)
Table of instrument state 3
634
R
Instrument state 4
bit
0 Sensor_broken
1 Over_heat
Table of instrument state 4
467
R
Instrument state
bit
0 AL.1 or AL.2 or AL.3 or AL.4 or
ALHB.TA1 or ALHB.TA2 or ALHB.TA3 or Power Fault
1 AL.Lo
2 AL.Hi
3 AL.Err
4 AL. Sbr
5 heat
6 cool
7 AL.LBA
8 AL.1
9 AL.2
10 AL.3
11 AL.4
12 ALHB or Power Fault
13 ON/OFF
14 AUTO/MAN
15 LOC/REM
Table of instrument state