EasyManuals Logo
Home>Generac Power Systems>Portable Generator>MAGNUM MMG75D

Generac Power Systems MAGNUM MMG75D User Manual

Generac Power Systems MAGNUM MMG75D
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Maintenance
40 MMG75D-100D Operating Manual 33701 C
4. Press to move the cursor (blue highlighted text) down to the Maintenance group.
5. Press to access the sections. Press to highlight the Maintenance section.
6. Press to access the parameters and highlight the maintenance alarm that needs to be reset.
7. Press to select the editable parameters. The cursor will highlight “Not Reset” under the selected mainte-
nance alarm. Press to highlight “Reset”.
8. Press to reset the selected maintenance alarm.
9. To perform additional maintenance alarm resets, repeat steps 6 - 8.
Note: If the selected maintenance alarm does not need to be reset, press to highlight “Not Reset” and press
to return to the parameters section.
10. To save changes, press and hold for five seconds. To discard changes made, press and hold O for five
seconds.
EXHAUST FILTER SERVICE REQUIREMENTS
The exhaust filter system contains a Diesel Particulate Filter (DPF). Over time, the DPF will require professional
servicing to remove ash buildup. The expected service interval will be at least 3,000 or 4,500 hours, based on engine
power and operating conditions. Actual service should take place when the indicator light appears on the Power
Zone™ controller. The DPF should be cleaned or replaced by an OEM authorized engine service dealer only. The
removal of DPF ash must be done by removing the DPF from the unit and placing it into specialized equipment.
CAUTION
Do not remove ash by using water or other chemicals. Removing ash by these methods
may cause equipment damage and create unsafe operating conditions.
CAUTION
Only a OEM authorized engine service dealer should remove, handle and dispose of DPF
ash. These materials may be considered hazardous under federal, state and local regula-
tions, and must be handled and disposed of properly.
To avoid unnecessary buildup of diesel particulates or soot in the exhaust filter system:
1. Utilize the Automatic Exhaust Filter Cleaning mode.
2. Avoid unnecessary idling.
3. Use proper engine oil. See the engine operator’s manual.
4. Use only ultra low sulfur diesel fuel. See the engine operator’s manual.
CHECKING GENERATOR DRIVE PLATE TORQUE
Follow the procedure below to check the torque of the generator drive plate bolts in accordance with the maintenance
chart.
1. Disconnect battery.
2. Remove generator fan guard.

Table of Contents

Other manuals for Generac Power Systems MAGNUM MMG75D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems MAGNUM MMG75D and is the answer not in the manual?

Generac Power Systems MAGNUM MMG75D Specifications

General IconGeneral
BrandGenerac Power Systems
ModelMAGNUM MMG75D
CategoryPortable Generator
LanguageEnglish

Related product manuals