50
10 Technical Parameters User Manual V1.0-2023-03-20
10 Technical Parameters
Technical Parameters GW320KH-
UT
GW350KH-
UT
GW320K-UT GW350K-UT
Input
Max. Input Voltage (V) 1500 1500 1500 1500
MPPT Operating Voltage Range (V) 480~1500 480~1500 480~1500 480~1500
MPPT Voltage Range for Nominal
Power
850~1300 850~1300 850~1300 850~1300
Start-up Voltage (V) 500 500 500 500
Nominal Input Voltage (V) 1160 1160 1160 1160
Max. Input Current per MPPT (A) 40 40 30 30
Max. Short Circuit Current per
MPPT (A)
60 60 50 50
No. of MPP Trackers 12 12 15 1 5
No. of Input Strings per MPPT 2 2 2 2
Output
Nominal Output Power (kW) 320 350 320 350
Nominal Output Apparent
Power(kVA)
320 350 320 350
Max. AC Active Power (kW) 352 350 352 350
Max. AC Apparent Power (kVA) 352 350 352 350
Nominal Output Voltage (V) 800, 3L/PE 800, 3L/PE 800, 3L/PE 800, 3L/PE
Nominal AC Grid Frequency (Hz) 50 / 60 50 / 60 50 / 60 50 / 60
Max. Output Current (A) 254 254 254 254
Output Power Factor ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Output THDi (@Nominal Output) <3% <3% <3% <3%
Eciency
Max. Eciency 99.0% 99.0% 99.0% 99.0%
European Eciency 98.8% 98.8% 98.8% 98.8%
Protection
PV String Current Monitoring Integrated Integrated Integrated Integrated
Internal Humidity Monitoring Integrated Integrated Integrated Integrated
Residual Current Monitoring Unit Integrated Integrated Integrated Integrated
PV Insulation Resistance Detection Integrated Integrated Integrated Integrated
Anti-islanding Protection Integrated Integrated Integrated Integrated