02 Safety Precaution User Manual V1.0-2023-03-20
DANGER
• Do not apply mechanical load to the terminals, otherwise the terminals can be damaged.
• All labels and warning marks should be visible after the installation. Do not scrawl,
damage, or cover any label on the device.
• Warning labels on the inverter are as follows.
2.4 Personnel Requirements
NOTICE
• Personnel who install or maintain the equipment must be strictly trained, learn about
safety precautions and correct operations.
• Only qualied professionals or trained personnel are allowed to install, operate, maintain,
and replace the equipment or parts.
DANGER High voltage hazard.
Disconnect all incoming
power and turn o the
product before working on it.
Delayed discharge. Wait
5 minutes after power o
until the components are
completely discharged.
Read through the user
manual before any
operations.
Potential risks exist. Wear
proper PPE before any
operations.
High-temperature hazard. Do
not touch the product under
operation to avoid being
burnt.
Grounding point.
CE Mark Do not dispose of the inverter
as household waste.Discard
the product in compliance
with local laws and
regulations, or send it back to
the manufacturer.
2.3 Inverter Safety
WARNING
• The voltage and frequency at the connection point meet the inverter grid connection
requirements.
• Additional protective devices like circuit breakers or fuses are recommended on the AC
side. Specication of the protective device should be at least 1.6 times the maximum AC
output current.
• Make sure that all the grounding cables are tightly connected. When there are multiple
inverters, make sure that all the grounding points on the enclosures are equipotental
connected.
• You are recommended to use copper cables as AC output cables. A copper to aluminum
adapter terminal is required when an aluminum cable is used.