GREE Photovoltaic Direct-driven Inverter Multi VRF Units
16
6.2 Circuit diagram of GMV-Y96WM/C-F(U) and GMV-Y120WM/C-F(U)
NOTICE!
This drawing is just for reference; please always refer to the electric wiring stuck to the
unit for actual wiring.
When conducting maintenance based on above circuit diagrams, units must be power-
strictly following the circuit diagrams when reconnecting the wires, otherwise, electric shock may occur.
7 UNIT OPERATING TEMPERATURE
Cooling Ambient temperature: -5ºC(23ºF)~52ºC(125.6ºF)
Heating Ambient temperature: -20ºC (-4ºF)~24ºC (75.2ºF)
In the case of a full fresh air conditioning IDU, the unit operating temperature is as follows:
Cooling Ambient temperature: 16ºC(60.8ºF)~45ºC(113ºF)
Heating Ambient temperature: -7ºC (19.4ºF)~16ºC (60.8ºF)
If unit operates out of the above range, it may not work stably and components may even be
damaged.