EasyManuals Logo
Home>Gree>Inverter>GMV5

Gree GMV5 Service Manual

Gree GMV5
321 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
GREE Photovoltaic Direct-driven Inverter Multi VRF Units
40
5.3 Allowable Pipe Length and Drop Height among Indoor and
Outdoor Units
Y type branch joint is adopted to connected indoor and outdoor units. Connecting method is shown
in the figure below.
Remark: Equivalent length of one Y-type manifold is about 0.5m (1-3/4feet).
L10: Length from the first branch to the farthest IDU;
L11: Length from the first branch to the nearest IDU;
Equivalent length of branch of IDU is 0.5m (1-3/4ft.).
R410A Refrigerant System
Allowable Value
m(ft.)
Fitting Pipe
Total length (actual length) of fitting pipe ≤1000(3280-3/4) L1+L2+L3+L4+…+L9+a+b+…+i+j
Length of farthest
fitting pipe m(ft.)
Actual length ≤165(541-1/4)
L1+L6+L7+L8+L9+j
Equivalent length ≤190(623-1/4)
Difference between the pipe length from the first
branch of IDU to the farthest IDU and the pipe length
from the first branch of IDU to the nearest IDU
≤40(131-1/4) L10-L11

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV5 and is the answer not in the manual?

Gree GMV5 Specifications

General IconGeneral
BrandGree
ModelGMV5
CategoryInverter
LanguageEnglish

Related product manuals