GREE Photovoltaic Direct-driven Inverter Multi VRF Units
41
R410A Refrigerant System
Allowable Value
Fitting Pipe
Equivalent length from the first branch to the furthest
piping (1)
≤40(131-1/4) L6+L7+L8+L9+j
Height difference
between outdoor
Outdoor unit at upper(2) ≤90(295-1/4) ——
Outdoor unit at lower(2) ≤90(295-1/4) ——
Height difference between indoor units ≤30(98-2/4) ——
Maximum length of Main pipe(3) <90(295-1/4) L1
From IDU to its nearest branch (4) ≤40(131-1/4) a,b,c,d,e,f,g,h,i,j
NOTICE!
(1) Normally, the pipe length from the first branch of IDU to the farthest IDU is 40m (131-1/4ft.).
Under the following conditions, the length can reach 90m (295-1/4ft.).
1) Actual length of pipe in total: L1+L2x2+L3x2+L4x2+…+L9x2+a+b+…+i+j≤1000m
(3280-3/4ft.).
2) Length between each IDU and its nearest branch a, b, c, d, e, f, g, h, i, j≤40m (131-1/4ft.).
3) Difference between the pipe length from the first branch of IDU to the farthest IDU and the
pipe length from the first branch of IDU to the nearest IDU: L10-L11≤40m (131-1/4ft.).
(2) When the maximum length of the main pipe from ODU to the first branch of IDU is≥90m
(295-1/4ft.), then adjust the pipe size of the gas pipe and liquid pipe of main pipe according to
the following table.
Outdoor Model Gas pipe size mm(in.) Liquid pipe size mm(in.)
GMV-Y72WM/C-F(U) No need to enlarge pipe size No need to enlarge pipe size
GMV-Y96WM/C-F(U) No need to enlarge pipe size Φ12.7(1/2)
GMV-Y120WM/C-F(U) No need to enlarge pipe size Φ15.9(5/8)
GMV-Y144WM/C-F(U) Φ34.9(1-3/8) Φ15.9(5/8)
GMV-Y168WM/C-F(U)
Φ34.9(1-3/8)
Φ19.05(3/4)
GMV-Y192WM/C-F(U)
Φ34.9(1-3/8)
Φ19.05(3/4)
GMV-Y216WM/C-F(U)
Φ34.9(1-3/8)
Φ19.05(3/4)
GMV-Y240WM/C-F(U)
No need to enlarge pipe size
Φ19.05(3/4)
GMV-Y264WM/C-F(U)
No need to enlarge pipe size
Φ22.2(7/8)
GMV-Y288WM/C-F(U)
No need to enlarge pipe size
Φ22.2(7/8)
GMV-Y312WM/C-F(U)
No need to enlarge pipe size
Φ22.2(7/8)
GMV-Y336WM/C-F(U)
No need to enlarge pipe size
Φ22.2(7/8)
GMV-Y360WM/C-F(U)
No need to enlarge pipe size
Φ22.2(7/8)
If the length between an IDU and its nearest branch is above 10m (32-3/4feet), then double the size
of the liquid pipe of IDU (only for the pipe size that is≤6.35mm (1/4inch).