GREE Photovoltaic Direct-driven Inverter Multi VRF Units
9
No Name Main Function
31 Liquid valve
Stop valve, closed when the unit is delivered from the factory and will be
opened after installation.
32 Gas valve
Stop valve, closed when the unit is delivered from the factory and will be
opened after installation.
33 Low-pressure measurement valve
Detects the low pressure value or charges refrigerant during system
running.
34 Oil balance valve
Stop valve, closed when the unit is delivered from the factory and will be
opened after installation.
35 Oil check valve
Checks the quality of refrigerating machine oil
of compressor during
maintenance.
36
Unloading valve
Avoid over-high pressure caused by pipeline blind spot.
37
Air by-pass valve
Avoids extra-high or low operating pressure.
38
Pressure-balanced valve
Ensures success startup of compressor.
4 BASIC PARAMETERS
4.1 Basic Parameter of Outdoor Unit
Outdoor Units_Heat Pump
8Ton
10Ton
Model
GMV-Y72WM/C
GMV-Y96WM/C
-F(U)
GMV-Y120WM/C
-F(U)
Module (combinated)
Cooling capacity
Btu/h
96000
120000
Heating capacity
Btu/h
108000
135000
Air volume
CFM
8240
8240
Max. external static
pressure
Pa 82 82 82
Noise(sound level)
dB(A)
61
63
Power
208/240V 3~ 60Hz 208/240V 3~ 60Hz 208/240V 3~ 60Hz
Input power for cooling
kW
5.45 7.30 10.00
Input power for heating
kW
5.80 7.85 10.50
Input current for cooling
A
16.42 20.37 26.27
Input current for heating
A
17.29 23.50 27.87
MOP
A
45(208V)/40(240V) 45(208V)/40(240V) 45(208V)/40(240V)
MCA
A
43.6(208V)/37.3(240V) 44.8(208V)/39.8(240V)
Compressor type
Inverter Scroll
Inverter Scroll
Compressor quantity N 1 1 1
Refrigeration oil no. of
compressor
FVC68D or FV68H FVC68D or FV68H FVC68D or FV68H
Oil
Charge
Compressor
L
1.1
1.1
Oil separate tank
L
4
4
Total L 4.6 5.1 5.1
Ambient temperature
range for cooling
23~125.6 23~125.6 23~125.6
Ambient temperature
range of heating
-4~75.2 -4~75.2 -4~75.2
Refrigerant type
R410A
R410A
Charging volume of
refrigerant
oz 229.3 398.6 416.2
Max. quantity of
connected indoor unit
unit 13 16 19
Size of gas pipe
in.
Φ7/8
Φ1-1/8