The figure below shows current curves that change with evaporating temperature and condensing
temperature while compressor works at 60Hz.
C
o
m
p
r
e
s
s
o
r
C
u
r
r
e
n
t
(
A
)
Evaporating
Temp. (°C)
Condensing
Temp. (°C)
The figure below shows current curves that change with evaporating temperature and condensing
temperature while compressor works at 90Hz.
C
o
m
p
r
e
s
s
o
r
C
u
r
r
e
n
t
(
A
)
Evaporating
Temp. (°C)
C
o
n
d
e
n
s
i
n
g
T
e
m
p
.
(
°
C
)
Note: You can infer from the preceding figures the current of compressors operating at other
frequency bands.
Step 2:
Check whether the compressor sounds sharp or rubs. Compare the sound of the faulty compressor
with that of a normal compressor.
Step 3:
Check whether the electric expansion valves of outdoor units and the 4-way valves can act normally,
and whether the oil return pipes and oil balance valves 1 and 2 are normal. Touch the pipeline next to the
oil return capillary tubes to check whether there is oil flowing.
Check method for each part: