GREE Air-ccoled Closed Control Unit Service Manual
6
4. Performance Parameters
Form 1
Class Item
Model
Unit
JKFD5CR/Na-E JKFD5QSR/Na-E
Code of Product EJ13000480 EJ13000440
Characteristics of Units
Total Cooling Capacity
/ Sensible Cooling
Capacity(22℃/50%)
kW 5.3/4.8
Total Cooling Capacity
/ Sensible Cooling
Capacity(24℃/17℃)
kW 5.5/5.1
Total Cooling Capacity
/ Sensible Cooling
Capacity(24℃/45%)
kW 5.4/4.9
Total Cooling Capacity
/ Sensible Cooling
Capacity(26℃/50%)
kW 5.7/5.2
Heating Capacity kW 2.7
Rated Humidifying
Capacity
kg/h 2
Air Flow Volume m
/h 1900 1900
External Static
Pressure
Pa 0 15
Acoustic Noise of
Indoor Units
dB(A)
58 56
Range of Temp. Controlling and
Precision
17~28℃±1℃
Range of Humidity and Precision 40~60%±5%
Power Supply 220V~ 50Hz
Cooling
System
Compres
Type Hermetic Scroll Type
Evaporat
Type Inner Screw Thread Pipe with Hydrophilic Film Aluminum Fin
Condens
Type Inner Screw Thread Pipe with Hydrophilic Film Aluminum Fin
Refrigerant R410A
Throttling Method Electronic Expansion Valve
Air Supply
System
Indoor
Unit
Fan
Type Low Noise and Centrifugal External-rotor
Type of
Direct Drive
Air Filter Type Plate Filter (G4)
Heating
S
stem
Heater Type Electric Heating
Humidifying
System
Humidifi
er
Type Infrared Type
Control Mode
Automatic Control by Mainboard
Indoor Unit
Indoor Unit Model
JKFD5CR/Na-E(I) JKFD5QSR/Na-E(I)
Dimensi
on
W mm
800 800
D mm
700 700
H mm
2250 1950
Net Weight kg
257 237
Outdoor Unit
Outdoor Unit Model
JKFD5P/Na-E(O)
Qt
Set
1
Condens
ing Fan
Type Low Noise Axial Type
Type of Drive Direct Drive
Noise dB(A)
60
Dimensi
on
W mm
900
D
mm 412
H
mm 1350