EasyManuals Logo
Home>Gree>Controller>XK19

Gree XK19 User Manual

Gree XK19
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
Wired Remote Controller XK19
15
3.14 Other Functions
(1). Lock
Upon startup of the unit without malfunction or under the “Off” state of the unit, press and
at the same time for 5s till the wired remote controller enters the Lock function. In this case, LCD
displays .
After that, repress these two buttons at the same time for 5s to quit this function.
Under the Lock state, any other button press won’t get any response.
(2). Memory
Memory switchover: Under the “Off” state of the unit, press Mode and at the same time for
5s to switch memory states between memory on and memory off. When this function is activated,
Memory will be displayed. If this function is not set, the unit will be under the “Off” state after power
failure and then power recovery.
(3). Selection of the Temperature Sensor
deriw eht ,rellortnoc etomer deriw eht rof tes neeb sah noitcnuf siht fI :yrevocer yromeM
remote controller after power failure will resume its original running state upon power recovery.
Memory contents: On/Off, Mode, set temperature, set fan speed and Lock function.
.
Indoor ambient temperature is sensed at the return air inlet(01 in the timer display area).
.
Indoor ambient temperature is the sensed at the wired controller(02 in the timer display area).
.
Select the temperature sensor at the return air inlet under the cooling, dry and fan modes,
.
Select the temperature sensor at the wired controller under the cooling, dry and fan modes,
and select the temperature sensor at the return air inlet under the heating mode and auto
while select the temperature sensor at the wired controller under the heating and auto
modes.(03 in the timer display area).
modes (04 displayed in the timer display area).
Under OFF state of the unit, press both Function and “Timer” for five seconds to go the
commissioning status. Under this status, adjust the display in the temperature display area to “00”
through the button “Mode”, and then adjust the option of the temperature sensor in the timer display
area through the button ▲ or ▼.
Pressing the button “On/Off” also can quit this commissioning status but the set data won’t be
memorized.
press, it will back to the previous state without memorizing the current data.
Under the commissioning status, if there is no any operation in 20 seconds after the last button
(4). Selection of the Fan Speed
Note:
After connected with indoor unit, if the type of ambient temperature sensor has not been manually
set, the wired controller will select the ambient temperature sensor according to the model of
connected IDU; if it connects to cassette type IDU, duct type IDU, floor ceiling type IDU, ceiling type
IDU, it will adopt , otherwise it will adopt . If the type of ambient temperature sensor is set
manually, the wired controller will subject to the manual setting, and will not set according to
automatic IDU model selection.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree XK19 and is the answer not in the manual?

Gree XK19 Specifications

General IconGeneral
BrandGree
ModelXK19
CategoryController
LanguageEnglish

Related product manuals