EasyManuals Logo
Home>Gree>Controller>XK49

Gree XK49 User Manual

Gree XK49
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
Wired Controller XK49
23
A8
Vacuum-pumping Mode
nL
Target low pressure modification
AH
Heating
nJ
High temperature prevention under
heating mode
AC
Cooling
nP
Temperature-adjusting value during
defrosting
AF
Fan
nU
Clear the remote control shielding order of
indoor unit
AJ
Filter Clean Reminder
5.4 Table of Debugging Codes
Error
Code
Content
Error
Code
Content
Error
Code
Content
U2
Outdoor Unit
Capacity
Code/Jumper Cap
Setting Error
UE
Refrigerant Charging is ineffective.
CH
Rated capacity is too
high.
U3
Phase Sequence
Protection of Power
Supply
UL
Emergency Operation DIP switch
setting of the compressor is wrong.
CL
Rated capacity is too
low.
U4
Protection of Lack of
Refrigerant
C0
Communication between indoor unit
and outdoor unit and the
communication between indoor unit
and wired controller have
malfunction.
CF
Error of Multiple Master
Indoor Unit
U5
Wrong Address of
Compressor Drive
Board
C2
Communication error between
master control and inverter
compressor drive
CJ
System addresses is
incompatible.
U6
Valve Abnormal
Alarm
C3
Communication error between
master control and inverter fan
motor drive
CP
Error of Multiple Master
Wired Controller
U8
Indoor Unit Tube
Malfunction
C4
Error of Lack of Indoor Unit
CU
Communication Error
between Indoor Unit
and Remote Receiver
U9
Outdoor Unit Tube
Malfunction
C5
Alarm of Indoor Unit Project
Number Collision
Cb
Outflow of Units IP
Address
UC
Master indoor unit is
successfully set.
C6
Alarm of Wrong Number of Outdoor
Unit

Questions and Answers: