Shenzhen Growatt New Energy CO.,Ltd
5
USB interface for system upgrade
Link-out for multi-cluster in parallel
communication
Link-in for multi-cluster in parallel communication
Terminal connect to ground
Stands for PACK cathode output
Figure 3: LED lights
Failure or protection status
1.3 Working Principle and Function
AXE 5.0L is an energy storage unit composed of electrochemical cells, switch button, battery
management unit, power and signal terminals, and mechanical parts.
It features better charge and discharge performance, more precise status monitor, longer cycle life,
and less self-discharge loss than other batteries.
The scalability is very strong, a single cluster can connect up to 10 batteries in parallel, and up to 8
clusters in parallel to expand the capacity and power of the energy storage system
The whole battery system communicates to Power Conversion System (PCS) via CAN.
Monitoring: voltage, current and temperature detection of both single cells and PACK.
Protection and Alarm: protection and alarm when overvoltage, under voltage, over current,
over-temperature or under temperature occurs. See Appendix I for details.
Report: report all alarm and status data to PCS.
Power off triggered by fault: PACK and PCS communication drop for 25 minutes or under
voltage protection for 2 minutes.