16
Restoring Factory Default Settings
Action Display Function/Parameter
Press the , or
keys as needed.
b
---
“B” Group selected
Press the key.
b
001
First “B” Group parameter
Press/hold until...
b
085
Country code for
initialization selected
Press the key. If setting
is correct, then skip next step.
02
00 = Japan
01 = Europe
02 = United States
To change country code, press
or key to set; to store.
Press the
key.
b
085
Country code for
initialization selected
Press the key.
b
084
Initialization function
selected
Press the key.
00
0 = disable initialization,
clear trip history only
Press the key.
01
1 = enable initialization
Press the key.
b
084
Initialization now enabled
to restore all defaults
Press/hold the and
keys, then press/hold the
key. Do not release yet.
b
084
First part of key sequence,
the “B” is flashing
Press/hold the (STOP)
key for 3 seconds.
b
084
Entire “B084” display will
begin flashing
Release the (STOP) key.
0EU
0USA
Default parameter country
code shown during initial-
ization process
Release the , , and
keys together.
d
001
Final part of key sequence,
function code for output
frequency monitor shown
after initialization is
complete
FUNC .
1
2
FUNC .
1
FUNC .
1
2
STR
FUNC .
2
FUNC .
1
STR
1
2
FUNC .
STOP
RESET
STOP
RESET
1
2
FUNC .