4.1 Fault Codes on the CM737
If a spanner is visible on the display there is an on ongoing alarm. Press the Info-button to view the fault code.
Supply water temperature sensor out of range
Outside air temperature sensor out of range
Case temperature out of range
Secondary pump or district heating supply
This fault code can just be seen in the fault history, parameter settings category 5.
Measured supply water temperature lies below 0°C or above 100°C.
Respond with ‘invalid data’ when thermostat asks for supply temperature Turn the
pump off, and enter off mode.
Outside sensor out of operating range. This fault code can only occur after the
measured outside temperature has been in range: -40°C to 60°C.
Measured outside temperature lies below -40°C or above 60°C
When the thermostat asks for the outside temperature the DHC will respond with
‘invalid data’.
After a reset this fault code will not occur again, until a valid temperature has been
measured, and then a non-valid temperature will be measured again.
Housing sensor out of operating range
Measured environment temperature lies below 0°C or above 60°C
Turn the pump off, and enter off mode
Secondary pump or district heating supply:
Cannot reach the set supply water temperature
Air in the pump, low temp/ not district heating supply
Thermostat doesn’t communicate by OT for 60 seconds
10 seconds after occurring, the DHC assumes an on/off thermostat is controller.
CH bit is cleared = 0.
Requested supply set point is cleared.
Fault is only cleared after a power cycle, OT thermostat is connected or
communication is working again.