Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15 117
Trouble
Code No.
Possible cause 1st. measure
2nd. measure
023
Detector unable to correctly
activate its base circuit board.
1) Fault occurs while loop is being
switched on:
switch off loop and switch back
on again after 1-2 minutes.
2) Fault occurs while switching the
base output:
check for connection of the
freewheeling diode necessary
for an inductive load. Pay
attention to switching capacity
of output.
3) Check whether the detector is
installed in a damp
environment.
Take any necessary
protective measures, e.g.
use mounting plate 781495
or base adapter 781497/98.
024
Detector unable to correctly
activate its base board.
Check whether detector is installed
in a damp environment.
Clear detector and re-check.
Take protective measure if
necessary, e.g., using
mounting plate 781495 or
781497/98.
025
A manual call point has
detected a short-circuit on its
external detector zone.
Check wiring of this detector zone
for short circuit.
---
026
An detector has recognised a
wire break on its external
detector zone.
Check wiring of this detector zone
for open circuit.
---
027
Error during measurement of
light absorption
Inform customer service ---
028
The detector has detected a
short-circuit behind its cut-off
relay.
Two detectors present with this
trouble
search for loop short
circuits between the two detectors.
One detector present with
this trouble
loop short
circuit between detector and
panel.
029
The sounder of the IQ8Quad
detector is defective.
Replace IQ8Quad detector and
return to manufacture.
---
030
The IQ8Quad detector cannot
emit the specified signal tone.
1. Check that the acoustic signal
is supported by the IQ8Quad
detector.
2. Check if the customer data has
been programmed correctly.
Notify Customer Service.
033 see 001 --- ---
034
esserbus
transponder is
defective
see 001 see 001
035
esserbus
transponder is
defective
see 001 see 001
036
Starke elektromagnetische
Störungen oder Melder ist
defekt.
see 004 see 004
037
esserbus
transponder has
identified fault with its external
voltage.
Check whether the external
switching voltage of the esserbus
transponder is in the correct
voltage range.
---
038
esserbus
transponder has
identified fault with its external
voltage.
Check whether the external
switching voltage of the esserbus
transponder is in the correct
voltage range.
---