Fire Alarm Control Panel IQ8Control C / M
96 FB 798951.10.GB0 / 04.15
10 Installer level – Commissioning / Maintenance
The Commissioning / Maintenance as well as Operations and Fire Alarm Control Panel functions which should
only be performed by specialised installers or authorised persons are integrated under the menu options
>Installer< in the FACP IQ8Control C/M. The service level is protected from unauthorised access by a numeric
authorisation code. This authorisation code is dependent on the >country function< programmed in the customer
data. Pressing the Installer function key moved from the service level to the installer level.
Before entry to the installer level, the authorisation code must be entered. (Exception: The requirement of the
authorisation code has been deleted by the programming of the Customer data). The authorisation for operations
in the Installer level remains active until the keyboard cover (key switch) is closed or no keyboard operation is
carried out in the installer level for more than ten minutes. During this period, access is possible to the various
display levels without further authorisation.
The menu options >Installer< is only displayed in the service level !
Indicated Display messages may differ due to object related programming.
A complete system check must be carried out after commissioning and for each modification of the
customer data programming!
Authorisation code (by factory default)
The authorisation code programmed at works level through the Country function can be changed individually in
the Customer data programming.
Code: 123 Country functions for (Germany, Great Britain, Switzerland and others)
20290 Country function for The Netherlands (NL)
--- Country function for Austria (no works programmed authorisation code)
Accsess Installer level
Code: * * * *
Escape Delete Select
Fig. 83: Entry of the authorisation code
Press the function key >Service< (The display changes to the service level)
Press the function key >Installer<
Enter the authorisation code (e.g. -123- for the Country function Germany on the keyboard)
Press function key >Select<
The Function menu of the installer level appears
Correcting an input error
An incorrect entry can be corrected with the >Delete< function key. Following the fourth incorrect entry, the
keyboard is blocked for approx. 60 seconds.
Installer code unknown
If the installer code is unknown or has been forgotten, it can be easily queried with the service PC. For this
purpose, the Customer data is obtained from the control panel by the tools 8000 software. The max. 8-digit
authorisation code is then displayed under menu options >Customer data - installer code<.
Storage of the Customer data which has only been queried to obtain the installer code is not necessary.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ESSER IQ8Control M and is the answer not in the manual?

Honeywell ESSER IQ8Control M Specifications

General IconGeneral
BrandHoneywell
ModelESSER IQ8Control M
CategoryControl Panel
LanguageEnglish

Related product manuals