Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15 95
4 Relay module (Part No. 787536)
Four dry relay contacts (not monitored) with programmable
operation mode normally open or normally close.
Contact rating: max. 30 V DC / 1 A
Quiescent current: approx. 10 mA.
Total current per module max. 1 A
1
23456
78
ext. device to relay K 1
ext. device to relay K 2
ext. device to relay K 3
ext. device to relay K 4
essernet
®
module 62.5 kBd (Part No. 784840.10)
network module for max. 16 network devices;
telephone cable IY (ST) Y x 2 x 0.8mm
Cable length between two devices max. 1000 m
Quiescent current: approx. 170 mA.
1
23456
78
L 1+
L 1-
not used
L 2+
L 2-
not used
not used
not used
essernet
®
module 500 kBd (Part No. 784841.10)
network module for max. 31 network devices; cable IBM type 1 or
similar cables;
Cable length between two devices max. 1000 m
Quiescent current: approx. 150 mA
Observe permitted torque (max. 0.4 Nm) of the terminals!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ESSER IQ8Control M and is the answer not in the manual?

Honeywell ESSER IQ8Control M Specifications

General IconGeneral
BrandHoneywell
ModelESSER IQ8Control M
CategoryControl Panel
LanguageEnglish

Related product manuals