Fire Alarm Control Panel IQ8Control C / M
122 FB 798951.10.GB0 / 04.15
Trouble
text
Possible cause 1st. measure 2nd. measure
start-up
An error has been detected
when an loop was switched
on; normal operation is
impossible.
Localise the source with
programming software tools
8000 switch on or reconfigure
the loop.
---
Detector >
When an loop was switched
on, more detectors were found
than programmed in the
customer data or more
detectors were found in an
EDD detector zone than
programmed in the customer
data.
Localise the source with
programming software tools
8000, switch on or reconfigure
the loop For EDD detector
zones, check the number of
detectors and reprogram the
customer data if necessary.
---
Detector <
When an loop was switched
on, fewer detectors were
found than programmed in the
customer data.
Localise the source with
programming software tools
8000, switch on or reconfigure
the loop.
---
Topolog.
The wiring configuration of this
loop cannot be precisely
determined.
Localise the source with
programming software tools
8000, switch on or reconfigure
the loop.
---
Serial No
A detector has been found in
the corresponding loop which
is not programmed in the
customer data.
Have detectors been
exchanged and is the error
plausible?
If yes, execute the Exchange
detector function for this loop
to update data.
Line A
The 1st ring is inoperable in a
redundant essernet
®
wiring.
The 2nd ring is in operation.
Check essernet
®
wiring
Check the essernet
®
switchover module and
replace if necessary.
Line B
The 1st ring is inoperable in
redundant essernet
®
wiring.
Check essernet
®
wiring
Check switch over module
and replace if necessary.
AD conv.
Fault of the A/D converter
card on the Basic module or
the A/D converter of the loop
module is defective.
Replace Basic module or
micro module.
---

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ESSER IQ8Control M and is the answer not in the manual?

Honeywell ESSER IQ8Control M Specifications

General IconGeneral
BrandHoneywell
ModelESSER IQ8Control M
CategoryControl Panel
LanguageEnglish

Related product manuals