Fire Alarm Control Panel IQ8Control C / M
42 FB 798951.10.GB0 / 04.15
Connection of the AC mains voltage and emergency power supply
For connecting the mains voltage (230 V AC) and emergency power supply, see Chapter 4.1.
N
L1
U
X2
Mains
230V~
Fig. 32: Connection of the AC mains voltage and batteries
Disconnect all power from the panel before carrying out any installation work! Observe before
connecting the AC mains voltage (e.g. 230 V AC) the specifications given on the panels nameplate
(adhesive label) inside the housing.
Connection terminals
removable
Fig. 33: Connection terminals removable
Observe permitted torque (max. 0.4 Nm) of
the terminals!
DIL Switch S2
S2
OFF
Normal operation Position "OFF" (factory setting)
S2
ON
Service mode Position "ON“
The LED V50 lits for an optical indication
The service mode will be activated after a panel reset and displayed at
the operation panel.
Reset Button S1
S1
Reset
Press the RESET button to restart the panel. Alarm and fault messages are reset, all
detector zones and primary loops are switched on and all changed switch settings are
read in.
A panel cold start using the RESET button is only possible when the housing contact (panel
housing) is open. If the panel interface was connected to the USB input, the connection is
detected only after a reset.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ESSER IQ8Control M and is the answer not in the manual?

Honeywell ESSER IQ8Control M Specifications

General IconGeneral
BrandHoneywell
ModelESSER IQ8Control M
CategoryControl Panel
LanguageEnglish

Related product manuals