Fire Alarm Control Panel IQ8Control C / M
76 FB 798951.10.GB0 / 04.15
Setting the essernet
®
address
The address of Network Micro Modules type 1 and 2 with hardware revision E and higher is set as a decimal
number by means of two rotary switches. Use an appropriate screwdriver for setting switches S1 (x1) and S2
(x10). The actual address is represented by the total of both values.
Adressing example e.g. Panel, address 9 or 21
Micro module
address
Schalterstellung Address factor Value
Σ = S1 x 1 + S2 x 10
S2 S1
9
S1 = x 1
9 x 1 + 0 x 10 = 9
S2 = x 10
21
S1 = x 1
1 x 1 + 2 x 10 = 21
S2 = x 10
Jumper configuration for the essernet
®
micro module type
If an essernet
®
micro module is used in the micro module slot, the integrated EMC filter must be set with jumpers
X27 to X30.
All jumpers in horizontal position
Required configuration for all micro modules apart from
essernet
®
(factory setting).
EMC protection for this micro module connection terminal
is activated.
X27 X28
X29 X30
All jumpers in vertical position
Only required for essernet
®
micro module.
The EMC protection is activated on the micro module for
essernet
®
and therefore switched off on the
basic module.
X27
X28 X29 X30
EMC protection of the essernet
®
cabling has to be ensured by appropriate external devices.