Fire Alarm Control Panel IQ8Control C / M
80 FB 798951.10.GB0 / 04.15
Adjustment of the relays
Relay Status Contacts switch S 1 Contact
K 1
10 k monitored
S 1
21
closed
not monitored
S 1
12
open
K 2
10 k monitored
S 1
43
closed
not monitored
S 1
34
open
K3
10 k monitored
S 1
65
closed
not monitored
S 1
56
open
No AC voltages may be applied to the relays built-into the Fire Alarm Control Panel. This applies also
to those relays operated in the >non-monitored< mode.
The >monitored / non-monitored< mode for individual relays must be programmed in addition to the
setting on the micro module using the service PC.