GSMV4G/GSMVCN4G Installation and Setup Guide
4-2
Primary Central Station ID (two-digit hexadecimal number)
Primary Subscriber ID (four-digit number)
MAC ID and MAC CRC number (located on the box and inside the communicator)
Once the communicator is registered, you may log out of the AlarmNet Direct website.
Register using the Tamper Switch
Initiate the registration sequence by clicking the Tamper Switch three times.
You can monitor the registration process by viewing the Status Display. The Message
(yellow) LED and the Status (green) LED will blink slowly in unison while registration is in
progress.
Once the registration has been completed successfully, the communicator enters normal
operating mode; the Status (green) LED goes out and the Message (yellow) LED is lit to
indicate that the Power On / Reset message is waiting to be sent. This message will appear
at the receiving station as “E339 C08xx”, where “xx” is the ECP device address. The
description may read “Trouble Exp. Mod. Reset”. If registration is not validated within 90
seconds, the communicator times out, and the (green) LED will be lit (solid).
The Power On / Reset message will be sent in Ademco High-Speed format if the
communicator is programmed for zone trigger, 4204 or 2x4204 modes.
If repeated registration attempts time out, verify the communicator account information has
been entered correctly.
Register using the Programming Tool
The interactive registration feature allows the installer to register the communicator
through a series of keyboard commands on the 7720P Programming Tool. This method of
registration lets the installer monitor the registration process.
Registering …
Once the installation is complete, press the
[
]
key on the 7720P.
The registration message is sent and the unit waits for the
acknowledgment.
Registration
SUCCESS
If this is a new installation and the city, central station, and
customer numbers have been correctly entered, the communicator
is registered and this message is displayed. The communicator is
now in full service and available for alarm reporting to the central
station.
Possible Errors
Registration BAD
Timed Out
Displayed if no response to the registration request is received.
Registration BAD
Pri Sub ID BAD
Indicates the city, central station, or customer number for the
labeled account(s) is not accepted. The ID information was either
entered incorrectly, or the central station failed to pre-authorize
programmed ID numbers with AlarmNet customer service.
Registration BAD
2nd Sub ID BAD
Indicates the city, central station, or customer number for the
Secondary account is not accepted. The ID information was either
entered incorrectly, or the central station failed to pre-authorize
programmed ID numbers with AlarmNet customer service.
Registration BAD
Pri&Sec IDs BAD
Displayed when both primary and secondary subscriber IDs are
invalid.

Table of Contents

Other manuals for Honeywell GSMV4G

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell GSMV4G and is the answer not in the manual?

Honeywell GSMV4G Specifications

General IconGeneral
BrandHoneywell
ModelGSMV4G
CategoryCell Phone
LanguageEnglish

Related product manuals