16 TK_S014 – Installation Manual
Figure 8 Free topology connection
Lonwork cables connection
Screw the twisted pair cable to LON-A and LON-B
The polarity of the LONWORKS
®
cables is not significant.
Figure 9 LON cable connectuion
A very common error in Lonwork cabling is to forget to terminate the lines; this can cause a variety
of unpredictable errors in the system; so please remember to add resistors terminators on the LON
cabling!
Refer to the above chapters on the different Lonwork wiring typologies for the related terminators details.
Connections of Reader cables
Connect the shielded cables coming from the readers to the terminal screws on the RTUA08 as shown in
Figure 10. The shields must be connected directly to the main earth ground.