T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
17 63-7147—05
Chilled Water Reset (continued)
Device Checkout
The T775 performance can be checked out to determine if
proper operation exists.
For example, when the outside air temperature is at 80° F
(27° C), the chiller water temperature should be 52.5° F
(11° C). See Fig. 17. Use the alternate Home screens to
check that the effective setpoint is adjusting correctly based
on the outside air temperature (Sensor B).
NOTE: The alternate Home screens do not show live
updates of the sensor temperature. They show the
temperature only at the moment the button is
pressed.
1. From the Home screen, use the button to verify
the setpoint temperature for each output.
2. Then, press the HOME button to view the actual
outside air temperature (Sensor B).
Fig. 17. Chiller setpoint vs. outside temperature.
Multi-Stage Boiler Control (No Reset)
– T775P
Application Description
The T775P is providing multistage boiler control based on the
boiler's discharge water temperature. The T775P uses the
fourth output relay to energize the primary pump.
Sensor Designation
This device application requires two sensors.
Sensor A is sensing discharge water and is used to control
3 boiler stages.
Sensor C is sensing the return water.
NOTE: Control can be to either Sensor A or C.
Operation
In this example, as the heating load increases, additional
stages of heat will cycle ON as the boiler water temperature
decreases. The T775P will stage three boilers to provide
sufficient heating. (See Fig. 18.) The primary circulating pump
energizes whenever any stage is energized.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
# Stages = 3 (T775 assigns pump to Relay 4)
Options
On Delay and Off Delay:
Seconds = 0 to 3,600 (default is 0)
Options WWSD = YES or NO
Temperature = 30 to 100° F (-1 to 38° C)
STG4/Pump: (Relay 4 controls the pump output)
Enable = YES
Exercise = YES or NO
Prepurge = -300 to 300 seconds (default is 0)
Postpurge = 0 to 300 seconds (default is 0)
NOTES:
1. A positive Prepurge time causes the pump to
energize before the first stage energizes.
A negative time causes the pump to energize
after the first stage energizes.
2. The Postpurge time causes the pump to run for
the set number of seconds after the last stage
de-energizes.
Return to the Setup menu, and select Alarms:
High Alarm = YES
High Limit = 220° F (93° C)
NOTE: This model has Equal Runtime options, which can be
configured with the Lead Lag output option in Setup.
Stages 1-3: Control to the discharge water temperature
Program for:
Setpoint = 200° F (93° C)
Throttling Range = 18° F (-8° C)
Sensor A
—Heat
IMPORTANT
After the desired value is selected, be sure to press
the or or HOME button in order to save that
value in the controller’s memory.
M24876
CHILLED WATER
SETPOINT TEMPERATURE
OUTSIDE AIR
TEMPERATURE
60°
45°
48.75°
52.5°
56.25°
70°
90°
85°
80°
75°

Table of Contents

Other manuals for Honeywell T775A2009

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell T775A2009 and is the answer not in the manual?

Honeywell T775A2009 Specifications

General IconGeneral
BrandHoneywell
ModelT775A2009
CategoryController
LanguageEnglish

Related product manuals