Hardware Description
1 Hardware Description
Issue 01 (2018-05-03)
168
Note the derating requirements of protection components when using protection components
such as fuses and circuit breakers.
The input circuit breakers of a PDF must match the output circuit breakers.
If the front-end PDF does not provide enough power inputs, configure a PDB that meets
the following requirements:
The current of each output of the AC PDB is not less than 18.5A.
The PDB must support dual-channel backup.
The input current of the PDB is not less than the sum of the current of the output
line.
1.8.6.8 HVDC PEM
The HVDC PEM is used to access the HVDC power supply. Each PEM provides four power
inputs. The two terminals on the right side are connected to the power supply plane on the
client side, and the two terminals on the left are connected to the power supply plane on the
client side. The HVDC PEM is fully configured with the entire system. The system has four
PEMs.
Appearance
Figure 1-71 shows the appearance of a HVDC PEM.
Figure 1-71 HVDC PEM
Panel
Table 1-90 Interface Description
Interface
Name
Description
Applicable power cable terminals
Power input
port
240 V HVDC and
380 V HVDC
power input ports
HVDC dedicated terminal