EasyManuals Logo
Home>Huawei>Inverter>SUN2000-60KTL-M0

Huawei SUN2000-60KTL-M0 User Manual

Huawei SUN2000-60KTL-M0
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
Parameter Description
Automatic OFF due to
communication interrupted
The standards of certain countries and regions require that the
inverter must shut down after the communication is
interrupted for a certain time.
If Automatic OFF due to communication interrupted is set
to Enable and the inverter communication is interrupted for a
specied time (set by Communication interruption
duration), the inverter will automatically shut down.
Automatic ON due to
communication resumed
If this parameter is set to Enable, the inverter automatically
starts after communication recovers. If this parameter is set to
Disable, the inverter needs to be started manually after
communication recovers.
This parameter is displayed when Automatic OFF due to
communication interrupted is set to Enable.
Communication interruption
duration (min)
Species the duration for determining communication
interruption. Used for automatic shutdown for protection in
case of communication interruption.
Soft start/boot time (s) Species the duration for the power to gradually increase
when the inverter starts.
Soft start time after grid failure
(s)
Species the time for the power to gradually increase when
the inverter restarts after the power grid recovers.
TCP heartbeat interval (s) Species the TCP link timeout period for the solar inverter to
connect to the management system.
TCP frame length Species the maximum length of the TCP frame sent by the
northbound device to the solar inverter.
Heartbeat period at application
layer (min)
Species the timeout period for the solar inverter to connect
to the management system.
Parallel communication mode Sets the communication mode between the master and slave
servers in SDongle scenarios.
----End
7.1.5.4 Setting Power Adjustment Parameters
Procedure
Step 1 Choose Function Menu > Settings > Power adjustment and set power
adjustment parameters.
SUN2000-(75KTL, 100KTL, 110KTL, 125KTL) Series
User Manual 7 Man-Machine Interactions
Issue 11 (2021-11-10) Copyright © Huawei Technologies Co., Ltd. 95

Table of Contents

Other manuals for Huawei SUN2000-60KTL-M0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-60KTL-M0 and is the answer not in the manual?

Huawei SUN2000-60KTL-M0 Specifications

General IconGeneral
BrandHuawei
ModelSUN2000-60KTL-M0
CategoryInverter
LanguageEnglish

Related product manuals