Check Item Expected Result Troubleshooting Maintenance
Interval
Power grid
environment
Input voltage:
380 V AC/400
V AC/415 V AC
(line voltage)
Output
voltage: 380 V
AC/400 V
AC/415 V AC
(line voltage)
If the input
voltage is
abnormal,
check the
power grid and
input cable
connection.
If the output
voltage is
abnormal,
check the UPS
running status
and check
whether an
alarm is
generated.
Monthly
LCD According to the
status icons on
the LCD, all units
are operating
properly. No fault
or alarm
information is
found in the
active and
historical alarm
records.
If an alarm is
present, rectify
the fault by
checking the
device status and
parameters.
Monthly
Cleanliness Wipe the cabinet
surface using a
white paper and
the paper does
not turn black.
Remove the dust,
especially from
the front panel.
Quarterly
Parameter
settings
The conguration
of the output
voltage grade,
frequency,
number of
batteries, and
battery capacity
meets
requirements.
Reset the
parameters.
Quarterly
UPS2000-G- (6 kVA-20 kVA)
User Manual 7 Routine Maintenance
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 104

Table of Contents

Other manuals for Huawei UPS2000-G-15KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-15KRTL and is the answer not in the manual?

Huawei UPS2000-G-15KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-15KRTL
CategoryUPS
LanguageEnglish

Related product manuals