D Alarm Handling
Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0001-01 Abnorm
al
mains
volt.
Minor Automa
tic
The rectier transfers to
battery mode, which does
not aect the power
supply to loads.
If no battery is installed,
the UPS shuts down.
Possible causes:
The mains voltage
exceeds 280 V.
The mains voltage is
less than 80 V.
The mains frequency
is not in the range of
40 Hz to 70 Hz.
The mains fuse is
abnormal.
Measures:
Check whether the
mains input voltage
is less than 272 V. If
not, wait until the
mains recovers.
Check whether the
mains input voltage
is greater than 88 V.
If the voltage is
greater than 88 V
and the Abnormal
mains volt. alarm
persists, the mains
fuse may be
abnormal. Replace
the faulty
equipment. If not,
0001-02
Abnorm
al
mains
volt.
Minor
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 143

Table of Contents

Other manuals for Huawei UPS2000-G-15KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-15KRTL and is the answer not in the manual?

Huawei UPS2000-G-15KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-15KRTL
CategoryUPS
LanguageEnglish

Related product manuals