Item 6 kVA 10 kVA 15 kVA 20 kVA
Humidity 0%–95% RH (non-condensing)
Altitude < 1000 meters
When the altitude ranges from 1000 m to 4000 m, the
output power is derated by 1% for each additional 100 m.
Storage and
transportation
temperature
–40°C to +70°C (battery pack: –20°C to +40°C)
9.3 Mains Input Electrical Specications
● For UPS2000-G-6 kVA and UPS2000-G-10 kVA, if the UPS input uses two live
wires (208 V/220 V system), all L and N wires change to L1 and L2 wires. If the
AC input of the UPS2000-G-10 kVA uses two live wires, connect AC INPUT L1,
L2, and L3 that are short-circuited with a short-circuit busbar to live wire L1,
and connect AC INPUT N to live wire L2.
● If the AC input of the UPS2000-G-15 kVA/20 kVA uses two live wires, connect
bypass and mains input bL1, bL2, bL3, mL1, mL2, and mL3 that are short-
circuited with a short-circuit busbar to live wire L1, and connect the input N
and N with a short-circuit busbar to live wire L2.
● In addition, if the AC input and AC output uses two live wires, the input and
output ends must connect to two-pole circuit breakers, that provided by the
user.
Table 9-4 6 kVA/10 kVA mains input electrical specications
Item
6 kVA 10 kVA
Input power
cable
Single-phase (L/N) input +
PE cable
● Single-phase (L/N) input +
PE cable
● Three-phase (L1/L2/L3/N)
input + PE cable
Rated input
voltage
220 V AC/230 V AC/240 V
AC
● 220 V AC, 230 V AC, or 240
V AC (single-phase input)
● 380 V AC, 400 V AC, or 415
V AC (three-phase input)
UPS2000-G- (6 kVA-20 kVA)
User Manual 9 Technical Specications