Battery mode
When the mains is abnormal or disconnected, the DC-DC step-up transformer
boosts the DC power supplied from batteries. Then the inverter converts the
DC power into stable AC power for powering loads.
Bypass mode
The mains supplies power directly to loads after
ltering. The UPS transfers to
bypass mode when overload, overtemperature, or faults occur. This mode
does not provide battery backup capability.
Economy control operation (ECO) mode
If the bypass voltage and frequency are in the
specied range, the UPS
supplies power to loads over the bypass. If the bypass voltage and frequency
are outside the range, the UPS transfers to normal or battery mode. ECO is
short for economy control operation.
NO TE
The 15 kVA/20 kVA UPS supports battery ECO mode in the case of two power sources.
In battery ECO mode, the bypass supplies power to the UPS, and batteries are used as
backup power. If the bypass is abnormal, the UPS transfers to battery mode.
By default, ECO mode described in this document refers to mains ECO mode.
UPS2000-G- (6 kVA-20 kVA)
User Manual 2 Quick Introduction
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 13

Table of Contents

Other manuals for Huawei UPS2000-G-15KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-15KRTL and is the answer not in the manual?

Huawei UPS2000-G-15KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-15KRTL
CategoryUPS
LanguageEnglish

Related product manuals