Table 4-35 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item Description Def
aul
t
Val
ue
Value
Range
Timed
shallow
discharge
test
Indicates whether to enable the scheduled
shallow discharge test. If this parameter is set
to Enable, the system automatically performs
a shallow discharge test when the test
interval arrives and the system meets the
shallow discharge conditions. The parameter
is
congurable in any mode.
Dis
abl
ed
Disabled
,
Enabled
Time
interval
Set the time interval for shallow discharge
tests. The parameter is congurable in any
mode.
60
day
s
30–90
days
Discharge
ratio
Set the proportion of the discharge capacity
to the total discharge capacity. The
parameter is congurable in any mode.
20
%
10%–
50%
Figure 4-43 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Table 4-36 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item
Description Def
aul
t
Val
ue
Value
Range
Test
noticati
on
Determine whether to periodically send
shallow discharge test notications. The
values include Disabled and Enabled. The
default value is Disabled. If the value is
Enabled, the system sends shallow discharge
test
notications. The parameter is
congurable in any mode.
Dis
abl
ed
Disabled
,
Enabled