116
*RST
Reset the instrument to original power on configuration. Does not clear Enable
register for Standard Summary Status or Standard Event Registers. Does not
clear the output queue. Does not clear the power-on-status-clear flag.
*TST?
Performs a self test of the instrument data memory. Returns 0 if it is successful or
1 if the test fails.
*CLS
Clears the Status Byte summary register and event registers. Does not clear the
Enable registers.
*OPC
Sets the operation complete bit (bit 0) in the Standard Event register after a
command is completed successfully.
*OPC?
Returns an ASCII “1” after the command is executed.
*WAI
After the command is executed, it prevents the instrument from executing any
further query or commands until the no-operation-pending flag is TRUE.
*ESR?
Queries the power-on status clear setting. Returns 0 or 1.
*ESE <value>
Standard Event enable register controls which bits will be logically ORed together
to generate the Event Summary bit 5 (ESB) within the Status Byte.
*ESE?
Queries the Standard Event enable register. Returns the decimal value of the
binary-weighted sum of bits.
*STB?
Read the Status Byte. Returns the decimal value of the binary-weighted sum of
bits.
*SRE <value>
Service Request enable register controls which bits from the Status Byte should
be used to generate a service request when the bit value = 1.
*SRE?
Queries the Service Request enable register. Returns the decimal value of