37
STV50 ed 09/08 VICTRIX 50 Rev. 002
Technical specications.
Technical specications, VICTRIX 50.
- e ue temperature values refer to an inlet temperature of
15°C and a ow temperature of 50°C.
- e maximum sound power emitted while the boiler is
working is < 55dBA. is measurement refers to tests in a
semi-anechoic chamber with the boiler working at maximum
heat output and with the extension of the ue accessories
complying with product standards.
Nominal heat input kW (kcal/h) 50,8 (43655)
Minimum heat input kW (kcal/h) 10,4 (8958)
Nominal (useful) heat output kW (kcal/h) 50,0 (43000)
Minimum (useful) heat output kW (kcal/h) 10,0 (8600)
Eective eciency 80/60 Nom./Min. % 98,5 / 96,0
Eective eciency 50/30 Nom./Min. % 106,0 / 106,5
Eective eciency 40/30 Nom./Min. % 107,0 / 107,0
Casing losses with burner On/O (80-60°C) % 0,47 / 0,20
Chimney losses with burner On/O (80-60°C) % 0,02 / 1,30
Maximum working pressure of heating circuit bar 4,4
Maximum working temperature of heating circuit °C 90
Heating temperature adjustment °C 20 - 85
Available head with 1000/h ow rate kPa (m H
2
O) 55,4 (5,65)
Full boiler weight kg 66,7
Empty boiler weight kg 63,0
Generator water capacity l 3,7
Power supply connection V/Hz 230/50
Nominal power input A 0,85
Installed electrical power W 180
Pump power absorption W 115
Fan power absorption W 59
Appliance electrical insulation - IPX5D
Max. ambient operating temperature °C +50
Min. ambient operating temperature °C -5
Min. ambient operating temperature with (optional) antifreeze kit °C -15
Max. ue gas temperature °C 75
NO
X
class - 5
Weighted NO
X
mg/kWh 55,0
Weighted CO mg/kWh 37,6
Type of appliance C13 / C33 / C63 / B23 / B33
Category II2H3B/P