E2 * It shows “Fail” in self-test
F * It shows “220Vac” in Utility Input.
8. In case of failure in self-test, the LCD display will illustrate from Drawing D to drawing E2, then an
error code or error status will be shown on the screen.
9. Your start-up operation of the UPS is completely now. Make sure the UPS is plugged onto the wall
receptacle for charging at least 8 hours and the batteries of the UPS are fully charged.
3.5.2 Start-up in Battery Mode (Cold Start)
1. Make sure the UPS you have has already been installed at least 1 set (20pcs) of 12V batteries.
2. Push the UPS On Switch
once for approx. 5 seconds to awake the UPS, and then the buzzer
sounds twice. The LCD display will illustrate from drawing A to drawing G, and keep awake for
approx. 15 seconds.
3. Press the UPS On Switch
of the UPS again for about 3 seconds till the LCD display illustrates
from drawing G to drawing H, then the UPS will be in self-test Mode. The UPS may offer energy
to the output in a minute, and the LCD display illustrates as drawing I. In case of failure in
pushing the UPS On Switch within 15 seconds, the UPS will automatically turn off. You then
have to go through step 1 to 3 once again.
G * It shows “Off”, which means the UPS
Prestart is successful.
H * It shows Utility input is “0” and Utility Abnormal.
I