The UPS offers CVCF (Constant Voltage Constant Frequency) setting function.
a. For correct setting and wiring, please contact with your local agent.
b. Do not do it by yourself; otherwise, your warranty will be void.
This UPS has been designed and constructed to protect your assets from the wide range of
power aberrations experienced on Utility power lines today. It is your insurance for reliable,
clean and stable voltage supply. It is worth taking care to install the system correctly and to
have it maintained correctly by your local dealer.
SAVE THESE INSTRUCTIONS - This Manual Contains Important Instructions that should be
followed during Installation and Maintenance of the UPS and Batteries.
Disconnection Device-CAUTION - A disconnect switch shall be provided by others for ac
output circuit. To reduce the risk of fire, connect only to a circuit provided with branch circuit
over-current protection for 32 amperes for 5-6Kva, 40 amperes for 8Kva and 50 amperes for
10Kva rating in accordance with the National Electric Code.
CAUTION - To reduce the risk of fire, unit input connect only to a circuit provided with branch
circuit over-current protection for 40 amperes for 5-6Kva, 45 amperes for 8kVA and 65
amperes for 10Kva rating in accordance with the National Electric Code.
Maximum ambient operating temperature 40C or equivalent
1.2 Storage Instruction
For extended storage through moderate climate, the batteries should be charged for 12
hours every 3 months by plugging the UPS power cord into the wall receptacle and turn on
input breaker on front panel. Repeat this procedure every 2 months under high
temperature environment.