26
7. Specifications
E
6
LCD 5000 RT E
6
LCD 6000 RT E
6
LCD 8000 RT E
6
LCD 10K RT E
6
LCD 10K RT TM
NPUT
Voltage Range (Vac) 160-280 277 - 485
Frequency (Hz) 45 / 65 Hz
Number of phases Single phase + ground
Three phase, R, S, T +
Neutral + Ground
Input Power factor > 0,99 (full load)
THD <6% <30%
OUTPUT
Voltage Range (Vac) 200/208/220/230/240 adjustable .(208/120 Vac in option)
Voltage adjustment Nominal voltage + 1%, + 2%, + 3%, - 1%, - 2%, - 3%
Voltage regulation ± 2%
Capacity (VA/W) 5000 6000 8000 10000 10000
Power Factor 0,7
Output wave form Sine wave, THD <3% (from 0 up to 100% in load)
Frequency stability ± 0,2% (battery mode)
Frequency regulation 3 Hz or 1 Hz (program by software)
Transfer time 0 ms
Crest factor 3:1
Efficiency Up to 90% (normal mode) ; Up to 95% Eco mode
Nominal autonomy > 5 min > 8 min > 5 min
Cold start Yes
BATTERY
Type Lead waterproof and without maintenance
Capacity 12V / 5 Ah 12 V/ 7 Ah 12 V/ 7 Ah 12 V/ 9 Ah
Quantity 20
Voltage (V) 240
Recharge time 4 hours at 90% 5 hours at 90%
DISPLAY
Status on LCD and LED Normal, Battery, Eco mode, Bypass, Battery low, Default battery, Overload, transfer default and Inverter default
Data specified on LCD
Input voltage, Input frequency, Output voltage, Frequency voltage, charge level, Voltage battery, internal
Temperature
Self-diagnostics
In mains mode, from control panel , by software and
auto test/ 24h
PROTECTION
Short circuit off mode immediately
Over heating Mains mode : Bypass Transfer - Battery Mode : Automatic shutdown
Low battery Alarm and automatic stop
EPO Stop immediate
Battery Electronic system of management of battery discharge
Leakage current <3mA in full load
ALARMS
Acoustics & display mains default, Low battery, Overload, environment default
PHYSICALS CHARACTERISTICS
Mechanicals dimensions
(wxhxd) mm
440x176x680 440x88x680 440x132x550 440x132x680
Input connectors At the bottom to the terminal
Output connectors At the bottom to the terminal
Net wei
g
ht + battery wei
g
ht
(kgs)
52 24+68 25+68 26+68 28+68
ENVIRONMENT
Operating temp, range 0-40°C
Warning temperature Battery design for use at 25°C. A higher ambient temperature will decrease its life span
Altitude 0-2000 m up to 40°C / 3000 m up to 35°C
Humidity 90% max without condensation
Noise < 50dB (at 1 m)
INTERFACE COMPUTER
Type Standard RS 232
Slots Second RS 232, USB, RS 485, relay card, SNMP/ Web card
compatible systems Windows 95/98/NT/2000/XP/Vista, Novell Netware, Linux etc
COMPLIANCE
Quality ISO 9001 certified manufacturing
Security EN62040-1-1, IEC 60950-1, UL 1778
Performance EN 62040-3
Standard EMC EN 62040-2, EN61000-3-2, EN61000-3-3, FCC Class A
Marking CE, cUL, UL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INFOSEC UPS SYSTEM E6 LCD-RT and is the answer not in the manual?

INFOSEC UPS SYSTEM E6 LCD-RT Specifications

General IconGeneral
BrandINFOSEC UPS SYSTEM
ModelE6 LCD-RT
CategoryUPS
LanguageEnglish

Related product manuals