INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 04 09 AA XX 201 19
15
3.5 Operation Test and Installation Instruction
3.5.1 Start Up in Normal Mode
1. Open the terminal block cover on the rear panel (refer to 0). Before start the installation, please
make sure the grounding is connected properly.
2. Make sure Utility breaker, UPS’ Utility breaker and Bypass breaker are on “Off” position.
3. Make sure the voltage of Utility matches with the input voltage window of the UPS.
4. Connect the Utility separately to the terminal blocks of UPS’ Utility and Bypass Inputs (If not
common). Switch on the Power Breaker of the distribution panel and the breakers of the UPS’ Utility
and Bypass Inputs, and then the UPS starts up. Green LEDs
& light up to show the Utility and
Bypass Inputs are normal and the LCD display with parallel function will illustrate from drawing A1,
drawing A2 to drawing B. Otherwise the LCD display will illustrate from drawing A2 to drawing B.
A1 A2.
B.
5. Then, the UPS is on Bypass Mode now and it will proceed self-test automatically. If there is no
abnormal message occurred, it means the pre-startup of the UPS is successful and the charger starts to
charge the batteries.
6. Press the UPS On Switch
for approx. 3 seconds, then
the Buzzer sounds twice and the LCD display changes from
drawing B to drawing C.
C
7. Then, the UPS is under self-test mode again, the LCD display will illustrate from drawing C to
drawing D and remain approx. 4 seconds under battery mode, then illustrate from drawing E1 to
drawing F if the self-test is successful.
D * It shows “test”.
E1 * It shows “OK” in self-test