- 33 -
Quick setup
Select command source
F0-02 Command source selection 1 0
0: Operation panel control (indicator 'LOCAL/REMOT' OFF)
1: Terminal control (indicator 'LOCAL/REMOT' ON)
2: Communication control (indicator 'LOCAL/REMOT' ashing)
Perform motor auto tuning
F1-37 Auto-tuning selection 0 3
0: No auto-tuning
2: Asynchronous motor dynamic auto-tuning
3: Asynchronous motor static auto-tuning(NEW)
NOTE: Motor won't rotate at this stage.
Steps of auto-tuning:
1. Make sure the UVW connection between the AC drive and motor is not
cut o by output contactor; if it is cut o, then manually handle with the
output contactor;
2. Set F1-37=3 and press
, the LEDs on the operating panel will display
"TUNE";
3. Press the key
on the panel, then the motor starts auto-tuning. It
usually takes about 30 seconds to nish this auto-tuning, wait until LEDs
stop displaying "TUNE";
4. Restore F0-02 to default value 1.
Select Control mode
F0-01 Control mode selection 2 0 or 2
0: SVC control
2: V/F control
Select frequency
reference source
F0-03 Main frequency source X selection 6 2 or 6
0: Digital setting F0-08 (pressing or can change F0-08 easily, and
the changed value won't be cleared even after power o)
1: Digital setting F0-08 (pressing
or can change F0-08 easily, but the
changed value will be cleared after power o)
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference setting
7: Simple PLC
8: PID
9: Communication setting