- 61 -
Parameter Table
Parameter Parameter Name Setting Range Unit Default Commission
F5-07 AO1 function selection
0: Running frequency
1: Set frequency
2: Output current
3: Output torque (absolute value)
N.A 3 -
Group F6: start and stop control
Parameter Parameter Name Setting Range Unit Default Commission
F6-00 Start mode
0: Direct start
1: Rotational speed tracking
restart
2: Pre-excited start
(asynchronous motor)
N.A 0 -
F6-03 Startup frequency 0.01 to 10.00 Hz 0.20 -
F6-04
Startup frequency active
set time
0.0 to 100.0 s 0.5 -
F6-05 DC injection 1 level 0 to 150 % 70 -
F6-06
DC injection 1 active set
time
0.0 to 5.0 s 0.5 -
F6-07
Acceleration/
Deceleration mode
0: Linear acceleration/
deceleration
3: S-curve acceleration/
deceleration C
N.A 3 -
F6-08
Time proportion of
S-curve at Accel start
0.0% to min. [(100.0% - F6-09),
80%]
% 80.0 -
F6-09
Time proportion of
S-curve at Accel end
0.0% to min. [(100.0% - F6-08),
80%]
% 20.0 -
F6-10 Stop mode
0: Decelerate to stop
1: Coast to stop
N.A 0 -
F6-11
DC injection 2 frequency
threshold
0.00 Hz to max. frequency Hz 0.10 -
F6-12
DC Injection 2 delay ON
set time
0.0 to 36.0 s 0.0 -
F6-13 DC injection 2 level 0 to 150 % 70 -
F6-14
DC injection 2 active set
time
0.0 to 5.0 s 0.5 -
F6-26
Time proportion of
S-curve at Decel start
0.0% to min. [(100.0% - F6-27),
80%]
% 50.0 -
F6-27
Time proportion of
S-curve at Decel end
0.0% to min. [(100.0% - F6-26),
80%]
% 50.0 -