Service menu
AirModule 6 720 813 268(2014/10)
46
12.3.2 Circuit 1 to 4 menu
Settings for each separate heating/cooling circuit are selected in this
menu. Here you can set the type of heating system installed for the
selected heating/cooling circuit. You can also set whether there is a
room controller or not, and which type of control mode to use. It is also
possible to optimise the heating/cooling circuit heating curves.
NOTICE: Risk of damaging the screed!
If an underfloor heating system is used, the max. flow
temperature recommended by the manufacturer of
the system should be observed.
Menu Item Setting range Description
Heating circuit installed No A heating/cooling circuit is not installed. If there is no heating/cooling circuit installed, the heat pump
module is used for DHW heating only.
On the heat source Electrical units and components in the selected heating/cooling circuit are directly connected to the heat
pump module (only possible with heating circuit 1).
At the module Electrical units and components in the selected heating/cooling circuit are directly connected to a MM100
module.
Programming unit HPC400 HPC400 independently regulates the selected heating/cooling circuit. No room controller installed.
CR10 CR10 installed as a room controller for selected heating/cooling circuit
CR10H CR10H installed with humidity sensor as a room controller for selected heating/cooling circuit
ext. room temp. sensor Yes An extra room temperature sensor has been connected to the room controller (CR10 / CR10H). It enables
the control of a second circuit from the same room controller.
No No additional room temperature sensor has been installed.
Heating system Radiator Preset of the heating curve, taking type of heat into consideration, e.g. curve characteristics and system
temperature
Convector heater
Underfloor
Circuit function Heating The selected circuit has a heating function only.
Cooling The selected circuit has a cooling function only.
Heating and cooling The selected circuit has both heating and cooling functions.
Control type Outdoor-temp.-
compensated
For more information on controlling the selected heating circuit ( Heating control mode, page 47)
Outside temp. with low end
Max. flow temperature 30 ... 75 ... 85(radiator)
30 ... 48 ... 60 °C
(underfloor heating system/
convector)
Maximum flow temperature from the heat pump module (booster heaters are used for temperatures
above the heat pump's maximum flow temperature).
Adjusting the heating curve Fine tuning the heating curve that has been preset through the heating system ( Setting the heating
system and the heating curves for outside temperature compensated control, page 47)
Heat constantly below Off The heating operates independently from the adjusted outside temperature in the active operating mode
( Constant heating below a certain outside temperature, page 49).
– 30 ... 10 °C If the adjusted outside temperature goes down below this set value, the heating will automatically change
from setback mode to heating mode ( Constant heating below a certain outside temperature, page 49).
Frost protection Instruction: Set outside temperature controlled frost protection to ensure the frost protection of the
entire system. This setting is independent of the set operating mode.
Outside temp. Frost protection is activated/deactivated depending on the temperature set here
( Temperature limit for frost protection (outside temperature threshold value), page 50)
Room temperature
Room and outside temp.
Off Frost protection off
Frost prot. limit temp.
(outside temperature
threshold)
– 20 ... 5 ... 10 °C Temperature limit for frost protection (outside temperature threshold value), page 50
Heating/Cooling Off
Automatic mode The heat pump will automatically switch between heating and cooling mode depending on the outside
temperature.
Constant heating The heat pump is only active in heating mode.
Constant cooling The heat pump is only active in cooling mode.
Heating mode off 10 ... 17 ... 30 °C When the outside temperature is below the value set here, the heating mode will turn on.
Cooling mode on off – 20 ... 28 ... 35 °C When the outside temperature is above the value set here, the cooling mode will turn on.
Heat immediately
temperature differential
1 ... 1 ...10 K When the outside temperature goes down below the heating deactivation temperature (setting value for
Heating mode off) with the value set here, heating mode will start immediately.
Cooling switch-off delay 1 ... 4 ... 48 h Cooling shutdown delay.
Cooling switch-on delay 1 ... 8 ... 48 h Cooling start delay.
Heating switch-on delay 1 ... 1 ... 48 h Heating shutdown delay
Table 30 Settings in the Heating/cooling circuit 1 to 4 menu