EasyManuals Logo
Home>IVT>Heat Pump>AirModule E 9

IVT AirModule E 9 User Manual

IVT AirModule E 9
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
Heat pump and heat pump module venting
AirModule –6 720 813 268(2014/10)
57
14 Heat pump and heat pump module venting
Fig. 49 Heat pump module and heating system
1. Connect the heat pump and heat pump module to the power.
2. Ensure that the circulation pump PC1 is running.
3. Remove the PC0 PWM plug from the circulation pump PC0 so that it
operates at maximum speed.
4. Activate the booster heater only.
5. Only deactivate the booster heater when the pressure has not
dropped in 10 minutes.
6. Connect the PC0 PWM plug to the circulation pump.
7. Clean the particle filter SC1.
8. Check the pressure on the pressure gauge GC1 and add more with
the fill valve VW2 if the pressure is below 2 bar.
9. Check that the heat pump is running and that there are no alarms.
10.Also vent via the other air vent valves of the heating system (e.g.
radiators).
T
T
6 720 809 156-22.1I
Z1
SC1
GC1
VC0
VL1
VC1
VW3
VW2
VC2
PC1
PC0
VW1
Fill preferably to a higher pressure than the final one so
that there is a magin when the temperature of the
heating system rises and the air that has been dissolved
in the water is vented out via VL1.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IVT AirModule E 9 and is the answer not in the manual?

IVT AirModule E 9 Specifications

General IconGeneral
BrandIVT
ModelAirModule E 9
CategoryHeat Pump
LanguageEnglish

Related product manuals