GB - 8
2.3 Technical data
Product description
1)
This value initiates the response of the hardware current limit. The maximum torque limit should be always below
this value, otherwise no more regulation is possible.
2)
The heat sink power loss is based on the losses of the power module and the rectier. There is no rectier power
loss at DC devices. The listed value must be dissipated via the mounting surface at at rear devices.
3)
At mains voltage >460 V multiply the nominal current with factor 0.86. Attention, with input rated voltage of 480 Vac
no braking resistor shall be connected.
4)
With sub-mounted lter in compliance with class C1 in accordance with EN 61800-3.
5)
Use E-MMC/ Type E - Manual Motor Controller according to UL508 / Class NKJH only. The following types are
accepted:
Manufacturer UL - File Type Required terminal line adaptor
Siemens E 156943
3RV1021-1xA10 3RV1928-1H
3RV1031-4xA10 –
ABB Stotz E 195536
MS325-xx S3-M3
MS450-xx –
Servo size 05 07 07 09
Housing size A A A A
Phases 1 3 1 3 3 3
Input rated voltage [V] 230 400
Output rated power [kVA] 0.9 1.6 1.8 2.8
Output rated current [A] 2.3 4 2.6 4.1
Stand still current [A] 2.5 4.4 2.9 4.5
Max. short time current
1)
[A] 4.6 8 5.2 8.2
OC-tripping current [A] 5.5 9.6 6.2 9.8
Input rated current [A] 4.6 3.2 8 5.6 3.6 6
Rated switching frequency [kHz] 8 8 8 4
Max. switching frequency [kHz] 8 8 8 8
Power loss at nominal operating [W] 38 35 55 50 65 65
Heat sink power losses
2)
[W] 28 25 45 40 55 55
Heat sink power losses (DC)
2)
[W] 25 22 40 35 52 50
Minimum braking resistor [Ω] 60 60 110 110
Typically braking resistor [Ω] 160 82 210 160
Maximal braking current [A] 7 7 7.5 7.5
Mains voltage U
N
3)
[V] 180…260 ±0 305…528 ±0
Mains frequency [Hz] 50…60 ±2
Output voltage [V] 3 x 0…U
N
Output frequency [Hz] 0…400
Max. motor line length (shielded)
4)
[m] 30
Max. motor line length (shielded) [m] 50
For use in USA
Max. mains fuse type RK5 [A] 10 6 15 10 6 10
Max. input fusing MMC type "E"
5)
[A] 10 6.3 16 10 10 10