Technical Data
2. Technical Data
2.1 Operating conditions
Standard Standard/
class
Instructions
Denitionacc.
EN 61800-2 Inverter product standard: ratedspecications
EN 61800-5-1 Inverter product standard: general safety
Site altitude
max. 2000 m above sea level
With site altitudes over 1000 m a derating of 1 % per
100 m must be taken into consideration.
Ambient conditions during operation
Climate
Temperature
EN 60721-3-3
3K3
extended to -10…45 °C (use frost protection for water
cooling systems and temperatures below zero)
With temperature over 45°C to max. 55°C a derating of
5 % per 1 K must be taken into consideration.
Humidity 3K3 5…85 % (without condensation)
Mechanical Vibration 3M1
Contamination
Gas 3C2
Solids 3S2
Ambient conditions during transport
Climate
Temperature
EN 60721-3-2
2K3 Drain heat sink completely
Humidity 2K3 (without condensation)
Mechanical
Vibration 2M1
Surge 2M1 max. 100 m/s²; 11 ms
Contamination
Gas 2C2
Solids 2S2
Ambient conditions for the storage
Climate
Temperature
EN 60721-3-1
1K4 Drain heat sink completely
Humidity 1K3 (without condensation)
Mechanical
Vibration 1M1
Surge 1M1 max. 100 m/s²; 11 ms
Contamination
Gas 1C2
Solids 1S2
Type of protection EN 60529 IP20
Environment IEC 664-1 Pollution degree 2
Denitionacc. EN 61800-3 Inverter product standard: EMC
EMC emitted interference
Cable-based interferences C3
1)2)
Earlier limit value A (B optional) according to EN55011
Radiated interferences C3
2)
Earlier limit value according to EN55011
Interference immunity
Static discharges EN 61000-4-2 8 kV AD (air discharge) and CD (contact discharge)
Burst - Ports for process meas-
urement control lines and signal
interfaces
EN 61000-4-4 2 kV
Burst - power interfaces EN 61000-4-4 4 kV
Surge - power interfaces EN 61000-4-5 1 / 2 kV Phase-phase / phase-ground
Electromagneticelds EN 61000-4-3 10 V/m
Cable-fed disturbances, induced
byhighfrequencyelds
EN 61000-4-6 10 V 0.15-80 MHz
MM
Voltage variation /
voltage drop
EN 61000-2-1 3
+10 % -15 %
90 %
Voltage unsymmetries /
Frequency changes
EN 61000-2-4 3
3 %
2 %
1)
This product can cause high frequency disturbances in residential areas (category c1) which require noise suppression measures.
2) Thespeciedvalueisonlymeetinconnectionwithacorrespondinglter.

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals