Annex
Annex A
A.1 Overload characteristic
30
60
90
120
150
180
210
240
270
300
0 105 110 115 120 125 130 135 140 145 150 160 170 180 190 200
210 220
Time [s]
Load [%]
Time [s]
Load [%]
30
60
90
0 105 110 115 120 125 130 135 140 145 150
Characteristic 1 Characteristic 2
The characteristic declines device-dependently in this range
(seeunitidentication).
On exceeding a load of 105% the overload integrator starts. When falling below the integrator
counts backwards. If the integrator achieves the overload characteristic that corresponds to
the inverter, the error E.OL is triggered.
A.2 Overload protection in the lower speed range
(only operating mode MULTI and SERVO)
E.OL2 E.OL
OC-tripping current
Short time current limit
Start of overload integrator
at 105%
Stand still current
(see technical data)
Min. frequency at continuous full load
(see technical data)
f [Hz]
Load [%]
APT1element(τ=280ms)startsifthepermissiblecurrentisexceeded.Afteritssequenceof
operation the error E.OL2 is triggered.

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals